Base Flashing

Also known as membrane base flashing · upstand · membrane upstand · wall flashing · parapet base flashing

The membrane flashing turned up from a low-slope roof onto walls, parapets and curbs, typically at least 8 in (200 mm) high, with a counterflashing lapped over its top edge.

5 min read5 sourcesNorth AmericaEuropeGlobal
Cite this entry"Base Flashing." roof.wiki. https://roof.wiki/base-flashing/ (accessed 2026-11-03).
Minimum height (North America)
8 in (200 mm) above finished roof
Minimum upstand (UK, BS 6229 / BS 8217)
150 mm (6 in)
Typical maximum without extra securement
About 12 in (300 mm)
Cant strip (asphaltic roofs)
About 3 × 3 in (75 × 75 mm); not needed for EPDM, PVC, TPO
Counterflashing piece length
Up to about 10 ft (3 m)
Lap onto field membrane
At least 4 in (100 mm), or per manufacturer

Base flashing is the strip of roofing membrane or flexible flashing material that is turned up from a low-slope roof surface onto a wall, parapet, curb or other vertical surface, sealing the junction where the horizontal roof membrane meets the upstand. It forms the lower half of a two-part flashing system: above it, a separate counterflashing (also called cap flashing or cover flashing), usually of sheet metal, is fixed to the wall and lapped down over the top edge of the base flashing so that water running down the wall cannot get behind it.3 In British and European usage the equivalent is the membrane upstand, covered by a metal or lead cover flashing.5

Structural deckVapour control layerInsulationCover boardWaterproof membrane Hot-air welding fuses overlapping sheets into one continuous skin
Inside a flat roof

Base flashing is a component of every low-slope roof and one of the main types of roof flashing. It differs from its siblings in where it sits and what it does: counter flashing covers and protects the top of the base flashing; roof edge metal closes the open perimeter of the roof where there is no wall; pitch pockets, boots and sleeves seal small penetrations; and the roof curb provides a raised frame around equipment and openings that is itself base-flashed. Base flashings are the single most leak-prone part of many low-slope roofs: one trade article estimates that close to 90 per cent of roof leaks occur at flashings and penetrations.2

Height

North American practice, reflected in trade and manufacturer guidance, is to carry base flashings at least 8 in (200 mm) above the finished roof surface, so that water ponding, driving rain, snow and ice cannot overtop the flashing.24 The US Department of Veterans Affairs master specification, for example, requires curbs to provide base flashing at least 200 mm (8 in) high, and roof expansion joint base flashings to end at least 200 mm (8 in) above the roof.1 Many manufacturers limit flashings to about 12 in (300 mm) unless additional securement is used, and typical installations run from about 8 to 14 in (200 to 350 mm) up the wall.23

In the United Kingdom, BS 6229 and BS 8217 require weatherproofing upstands at abutments, rooflights and service penetrations to be at least 150 mm (6 in) high, measured from the finished roof surface, including any paving, walkway or green roof build-up; reduced upstands of 75 mm (3 in) are accepted at door thresholds only with additional drainage and detailing.5

Roof deckWaterproofing + root barrierDrainage layerFilter fabricGrowing medium Vegetation
Layers of a green roof

Materials

Base flashing is normally made from the same family of material as the roof membrane, so that it can be bonded or welded to the field sheet:

  • Built-up and modified bitumen roofs use reinforced modified bitumen flashing sheets, often in two plies, set in hot steep asphalt, cold adhesive or torch-applied; the top edge is nailed or fastened to prevent the heavy sheet slumping down the wall.24
  • Single-ply roofs (EPDM, TPO, PVC) use unreinforced or reinforced flashing membrane of the same polymer, fully adhered to the upstand and seamed to the field membrane with tape or hot-air welding.4
  • Liquid-applied systems use a reinforced coat of the same resin.

Base flashings are typically fully adhered to the substrate, even where the field membrane is loose-laid or mechanically attached.4 On asphaltic roofs, a cant strip, a triangular wood or fibreboard fillet commonly about 3 in by 3 in (75 by 75 mm), is placed in the corner so that the membrane makes two 45° bends rather than one sharp 90° bend; cants are not needed with EPDM, PVC or TPO.3 The substrate behind the flashing, such as masonry, concrete, gypsum board, plywood or wood blocking, must be primed or prepared as the manufacturer requires.2

Termination and counterflashing

The top edge of the base flashing must be held mechanically, not just stuck, because heavy flashing sheets creep and slip and adhesives lose grip over time. Common methods are a fastened termination bar with sealant above, a row of nails or fasteners through the top of the sheet into a wood nailer, or securement behind a counterflashing.24 The flashing itself should not be relied on to hold down the field membrane; the membrane is secured at the base of the wall by a separate row of fasteners or a fastening strip.3

The counterflashing then covers the termination. Types include:

  • Reglet counterflashing, set into a groove cut or cast into the wall, which may be as shallow as 1 in (25 mm), or occasionally run through the wall.3
  • Surface-mounted counterflashing, fixed to the face of the wall with fasteners and a sealant bead along the top.
  • Two-piece counterflashing, with a receiver permanently built into the wall and a removable lower piece that can be unclipped for repair or reroofing.3
  • Through-wall flashing in masonry walls, which also collects water inside the wall and weeps it out above the roof.

Counterflashing pieces are usually limited to about 10 ft (3 m) in length, with lapped or slip joints that allow thermal movement while staying watertight.3 One public specification uses 1.3 mm (0.050 in) aluminium for three-piece counterflashing, lapped at least 100 mm (4 in) over the base flashing, with fastener screws at about 450 mm (18 in) centres.1

Installation

  1. Prepare the upstand. Provide a solid, dry substrate, wood nailers where needed, and a cant on asphalt roofs.3
  2. Secure the field membrane at the base of the wall with fasteners or a fastening strip.3
  3. Apply the base flashing as a separate layer from the field membrane, bonding it to the upstand and lapping it at least 4 in (100 mm) onto the roof membrane or as the manufacturer specifies.4
  4. Reinforce corners with prefabricated corners, butterfly patches or mastic and mesh.2
  5. Terminate the top edge with a termination bar, fasteners or counterflashing receiver.4
  6. Install the counterflashing the same day if possible; if not, protect the open top with a temporary three-course seal of mastic, fabric and mastic.2

Penetrations such as pipes and conduits should be kept at least 2 ft (600 mm) from walls and other upstands so that they can be flashed properly.2

Performance, maintenance and failure modes

Common problems include:

  • Slumping or slipping of heavy modified bitumen flashings that were not fastened at the top.24
  • Splitting or opening of laps at the turn-up, especially where the roof and wall move independently; flexible tubing or expansion details may be needed at the roof-to-wall joint.3
  • Membrane shrinkage in some single-ply sheets, which can pull flashings away from walls and corners.3
  • Sealant failure at exposed joints and counterflashing fasteners, which stay watertight only for a limited time.3
  • Insufficient height, which allows ponding water, snow or wind-driven rain to overtop the flashing.5
  • Water bypassing the flashing through porous masonry, open copings or missing through-wall flashings above.3

Inspections should check the top termination, laps, corners and counterflashing, and the condition of the wall and coping above. Base flashings are normally replaced when the roof membrane is replaced, and two-piece counterflashings make that easier by allowing the cover to be removed without cutting into the wall.3

Sources

Reviewed 2 November 2026 · 5 sources · 5 cited inline · Editorial policy · Plain-text version · Suggest a correction

  1. VA Master Construction Specification 07 71 00 Roof SpecialtiesU.S. Department of Veterans Affairs / WBDG · wbdg.org
  2. Technical Details: Elements of Proper Flashing ApplicationsRoofing Contractor · roofingcontractor.com
  3. Flat Roof-to-Wall FlashingsASHI Reporter · homeinspector.org
  4. Roofing details: curbsBuilding Enclosure · buildingenclosureonline.com

From the community

Know this topic first-hand? Share a photo you took, a correction with a source, or local knowledge. Every contribution is reviewed before it appears.

Contribute to Base Flashing

Loading…