A roof curb is a raised frame built or installed on a roof deck to support and weatherproof something that sits on or passes through the roof, such as a rooftop HVAC unit, exhaust fan, skylight, smoke vent, roof hatch or a grouped set of pipes and ducts. The curb lifts the opening above the roof surface so that the roof membrane can be turned up its sides as base flashing and lapped by a metal cap or by the equipment itself, keeping ponding water, snow and wind-driven rain out of the opening.2
Curbs are used mainly on low-slope roofs and are a key detail in roof flashing. They differ from related details as follows: a pitch pocket seals an irregular penetration with poured sealer rather than lifting it on a flashed frame; a pipe boot or sleeve seals a single round penetration; and an equipment support or rail carries equipment on posts or sleepers without an opening through the roof. Skylight curbs are closely related to the kerbs or upstands used for skylights and roof lanterns.
Types
- Field-built curbs are framed on site from treated timber or steel, sheathed, insulated and then flashed by the roofer.
- Prefabricated (manufactured) curbs are factory-made boxes of galvanised steel or aluminium, usually with an integral wood nailer at the top and a flashing flange at the base, delivered to suit a particular unit. One manufacturer's range uses 18-gauge galvanised steel or 0.063 in (1.6 mm) aluminium for curbs under 50 in (1,270 mm) square and 16-gauge steel or 0.080 in (2.0 mm) aluminium for larger ones, with heavier gauges for heavy-duty curbs.3
- Insulated curbs contain rigid insulation, commonly 1 to 1.5 in (25 to 38 mm) of rigid glass fibre board, to reduce heat loss and condensation inside the curb.3
- Pitched (sloped) curbs have a bottom that matches the roof slope, specified as a rise-to-run ratio such as 3:12, and a level top so that equipment sits level on a sloping roof.3
- Sound curbs are taller, insulated curbs designed to reduce equipment noise transmitted into the building.3
- Curb adapters and extensions raise an existing curb to give more flashing height after reroofing, or adapt an old curb to a new unit of a different size.3
- Skylight and hatch curbs, often supplied integrally with the unit.
Public specifications commonly call for extruded aluminium curb frames; one federal specification sets a minimum of 2 mm (0.080 in) for three-piece curb sections.1
Height
The general North American rule is that curbs should rise at least 8 in (200 mm) above the finished roof surface, so that the base flashing can be at least that high.12 One university construction standard adds that the curb must also be at least 8 in above the level of any emergency overflow pipe or scupper, if that is higher, since water can rise to that level when drains block.5 Prefabricated curbs are commonly made in heights from about 8 to 24 in (200 to 600 mm) or more, and taller curbs are used where thick insulation or overburden will be added or where snow accumulates.3 The roof drainage design should keep curbs out of drainage valleys and away from drains.
Flashing a curb
- Set and secure the curb to the structural deck, with its base flange on the deck or insulation as the system requires.
- Install insulation and cants as needed, and tie the roof membrane to the base of the curb.
- Apply base flashing up the curb sides as a separate layer from the field membrane, fully adhered to the curb even on loose-laid or mechanically attached roofs, and extending at least 4 in (100 mm) out onto the roof membrane, or as the manufacturer specifies.23
- Terminate the top of the flashing over the wood nailer with fasteners, a termination bar or a metal counterflashing, to stop heavy flashing sheets slumping.2
- Counterflash with the equipment's own skirt, a metal cap or a separate counterflashing. Where the equipment housing acts as the counterflashing, the curb must be flashed before the unit is set.
- Seal the curb interior at duct openings so that conditioned air and moisture do not leak into the roof assembly.
Crickets
On sloped or tapered roofs, a curb across the flow of water acts as a dam. The International Building Code requires a cricket or saddle on the ridge (upslope) side of any chimney or penetration more than 30 in (762 mm) wide measured perpendicular to the slope, covered with sheet metal or the same material as the roof covering.6 Large curbs on low-slope roofs are therefore typically given tapered insulation crickets to divert water around them.
Equipment supports and rails
Where equipment does not need an opening through the roof, it is often mounted on equipment rails (sleeper curbs) or on stands with flashed posts. Equipment rails are long, narrow curbs, commonly 4 to 8 in (100 to 200 mm) wide and 8 to 14 in (200 to 350 mm) high, mounted to the deck and roofed and flashed like any other curb.3 The National Roofing Contractors Association suggests curbs rather than open stands where possible, so that no work is needed beneath units during reroofing and maintenance; where stands are used, the unit must be high enough above the roof for proper roofing and repairs beneath, and round pipe or square tube legs are easier to flash than steel angles or wide-flange sections.4 Flashing collars around such legs are carried at least 8 in (203 mm) above the roof.4
Spacing and layout
Curbs and penetrations should be laid out so that every side can be flashed properly; a common rule is to keep penetrations at least 2 ft (600 mm) from walls and other upstands.2 Narrow gaps between curbs, or between a curb and a parapet, make it impossible to install and inspect flashings and trap water and debris.
Performance, maintenance and failure modes
Curbs are a frequent leak source because they combine a membrane upturn, a top termination, a counterflashing and an equipment seal, often disturbed by service technicians. Common problems include:
- Insufficient height after reroofing, when added insulation reduces the exposed curb height below the 8 in minimum.15
- Flashing slump where heavy flashing sheets were not mechanically fastened at the top.2
- Water entry at the top of the curb or through the equipment gasket.2
- Ponding on the upslope side of wide curbs without crickets.6
- Condensation and rot in uninsulated or poorly sealed timber curbs.
- Damage by service traffic, which is reduced by walkway pads around equipment needing frequent servicing.5
Inspection should cover the base flashing laps and corners, the top termination, the counterflashing or equipment skirt, sealants, and the condition of timber nailers. When roofs are replaced, curbs are often raised with adapters so that the new insulation does not leave the flashing too low.3
Sources
Reviewed 2 November 2026 · 6 sources · 6 cited inline · Editorial policy · Plain-text version · Suggest a correction
- VA Master Construction Specification 07 71 00 Roof SpecialtiesU.S. Department of Veterans Affairs / WBDG · wbdg.org
- Roofing details: curbsBuilding Enclosure · buildingenclosureonline.com
- Roof Curbs, Extensions and Support InformationGreenheck (via Industrial Stores) · industrialstores.com
- Manual Elements: rooftop equipment supports and penetrationsProfessional Roofing (NRCA) · professionalroofing.net
- Construction Standards 07 70 00 Roof and Wall Specialties and AccessoriesDuke University Facilities · facilities.duke.edu
- Roofing code: weather protectionBuilding Enclosure · buildingenclosureonline.com