Lightweight insulating concrete (LWIC) is a site-mixed, pumped concrete of very low density that is placed on top of a structural roof deck to form the substrate for a low-slope roof membrane. The American Concrete Institute defines insulating concrete as having an oven-dry unit weight of 50 lb/ft3 (800 kg/m3) or less, made from Portland cement, water and air, with or without lightweight aggregate.1 The low density comes either from expanded mineral aggregates (vermiculite or perlite) or from a pre-formed foam that fills the mix with tiny air cells; the latter is called cellular concrete.12
As a roof system, LWIC is usually combined with boards of moulded expanded polystyrene (EPS) embedded within it, which supply most of the thermal resistance, while the concrete encapsulates the boards, provides a firm and nailable top surface, and is screeded to slope. The result is a monolithic insulated deck with built-in drainage slope, which is why LWIC is classed among roof deck systems as well as roof insulation.1
How it differs from other insulation methods
Most low-slope roofs are insulated with rigid boards such as polyiso, EPS or mineral wool fastened or adhered to the deck, with slope created by tapered insulation. LWIC differs in three ways:
- It is wet-placed. The material arrives as a slurry and is pumped, so it fills deck flutes and irregularities and can be shaped to any drainage pattern.
- It is the attachment substrate. The membrane's base sheet is fastened into the cured concrete rather than through insulation into the steel deck below.1
- It is stiffer and more fire-resistant than board insulation: LWIC is three to 20 times stronger in compression than common roof boards, and cellular concrete filling the flutes of a steel deck can eliminate the need for underside fireproofing in some assemblies.13
Its drawback is water: the mix carries water onto the roof that must escape before or after the membrane goes on.
Materials
- Vermiculite — the predominant aggregate historically; it exfoliates at about 980 C (1,800 F) into a platy material of 6-9 lb/ft3 (96-144 kg/m3), holds water for cement hydration and helps build slope with little cracking.1
- Perlite — volcanic glass expanded above about 870 C (1,600 F) into a low-density, closed-cell particle. Some perlites react with cement alkalis and expand, so perimeter and penetration control joints are recommended.1 One US federal specification requires 25 mm (1 in) compressible control joints around the perimeter and penetrations for perlite concrete.2
- Cellular (foam) concrete — cement, water and a foaming agent. Its water/cement ratio is about 0.50-0.60, far lower than the 1.50-2.00 of aggregate mixes, which shortens drying.3 The same federal specification calls for cellular concrete where single-ply membranes are adhered directly.2
- EPS boards — ASTM C578 Type I is preferred; boards range from about 1 to 16 in (25-400 mm) thick, give roughly R-4 per inch (RSI 0.7 per 25 mm), and are perforated so the concrete flows through and locks the system together.1 One specification asks for about 3% open area in the holes or slots.2
Typical US federal requirements for the cured concrete are a minimum compressive strength of 125 psi (862 kPa) tested to ASTM C495 and a maximum dry density of 28 lb/ft3 (450 kg/m3), placed 2-8 in (50-200 mm) thick.2 A cellular-concrete manufacturer recommends at least 200 psi (1.4 MPa) with fibre reinforcement.3
Substrates and venting
LWIC is placed on galvanised steel deck, on structural concrete, or on a sound existing built-up roof. Galvanised, bottom-slotted 1-1/2 in (38 mm) "B" deck has become the usual steel substrate because the slots let water vapour escape downward.1 Where the deck is not slotted, as on concrete, moisture must be released through topside relief vents in the membrane and through edge venting.12 The federal guide specification requires relief vents at least 6 in (152 mm) in diameter at no more than 30 ft (9 m) from one another or from a vented edge, cut down to the structural deck, while noting that some hot-humid climates such as the US Gulf Coast may be better unvented according to ASHRAE criteria.2
Installation
A typical LWIC-over-EPS roof is built as follows:12
- Prepare the deck — clean galvanised slotted steel deck, or concrete with vents planned.
- Place a slurry coat of LWIC at least 1/8 in (3 mm) thick, filling the deck flutes.
- Set the EPS boards into the wet slurry in stepped thicknesses to create slope to drains — at least 1/4 in per ft (1:50) under the federal specification.
- Pour the top coat of LWIC to cover the boards by at least 2 in (50 mm), or the steel deck crests by at least 3-1/2 in (90 mm) where no EPS is used, and screed to slope without birdbaths.
- Add reinforcement where required — wire mesh is placed at mid-depth on slopes steeper than 4:12, in fire-rated assemblies on metal deck, and in seismic regions.
- Cure to ACI 308; no traffic is allowed for 72 hours, and placement stops below 4 C (40 F) or when rain, snow or ice is present. Frozen material is removed and replaced.
- Install the roof — usually a base sheet fastened with fasteners designed for LWIC, vented at the perimeter, followed by the membrane. Built-up membranes are not adhered directly to LWIC.1
For cellular concrete, a membrane can often be applied about 3-5 days after casting, and fully adhered systems a few days after, subject to a test patch for smooth-surfaced membranes.3 Base-sheet fasteners are checked by pull-out tests; one specification requires each to resist at least 30 lb (14 kg), with one test per 10 squares (about 93 m2) or at least three tests.2
Performance and failure modes
Well-built LWIC decks combine slope, insulation, fire resistance and a monolithic surface that blocks air leakage from the building, which helps achieve high wind-uplift ratings without a separate air barrier.3 LWIC systems had been in use for more than 60 years by the late 1990s, and the ACI identified low-slope roofing as their largest single use.1
The characteristic problems are:13
- Blistering of the membrane from residual mix water, especially when the deck was placed in wet months or was not vented (see roof blistering);
- Shrinkage cracking when the concrete is left exposed or is under-reinforced, letting rain into the deck;
- Variable strength and low fastener pull-out where the mix or curing was poor;
- Freeze damage that scales or dusts the surface;
- Alkali expansion with some perlite sources;
On re-roofing, LWIC is often kept: the old membrane is removed, the surface is evaluated by moisture survey and pull-out tests, and wet or damaged areas are cut out and patched before a new base sheet is fastened (see roof moisture survey and insulation fasteners and plates).
Where it is used
LWIC is used mainly in the United States on commercial, institutional and government buildings with steel or concrete decks, particularly schools, offices and warehouses where a sloped, fire-resistant and durable substrate is wanted. US Department of Veterans Affairs master specifications include it as a standard section,2 and it appears in many other public and commercial specifications for low-slope roofs on steel and concrete decks.1