Cap nails are short roofing nails that carry a wide, flat washer — a cap — of plastic or thin metal under the head. The cap spreads the holding force over a larger area of the sheet being fastened, so that light materials such as felt, synthetic underlayment, house wrap and insulation facers are less likely to tear around the nail or blow off before the roof covering is installed. Cap nails are driven by hand or with pneumatic cap nailers, which feed caps and nails from separate coils; cap staples with a similar cap are an alternative where codes allow them.12
Under the parent topics of roofing underlayment and roofing fasteners, cap nails are the standard fastener for mechanically attached underlayments. They differ from insulation fasteners and plates, which use much larger 3 in (76 mm) plates to hold rigid boards on low-slope roofs, and from ordinary roofing nails used for shingles, which have 3/8 in (9.5 mm) or larger heads but no cap.
Specifications
The US model codes specify cap fasteners for underlayment in high-wind areas, and the same dimensions are widely used elsewhere:12
- Cap diameter — at least 1 in (25 mm), metal or plastic.
- Metal caps — sheet metal at least 32 gauge; power-driven metal caps at least 0.010 in (0.25 mm) thick.
- Plastic caps — outside edge at least 0.035 in (0.89 mm) thick.
- Shank — corrosion resistant, annular-ring or deformed shank at least 0.083 in (2.1 mm) in diameter, or smooth shank at least 0.091 in (2.3 mm).
- Staples (where permitted) — at least 21 gauge.
- Length — long enough to penetrate the roof sheathing, or at least 3/4 in (19 mm) into it.
In practice, plastic caps dominate for synthetic underlayments because they are light, do not corrode and seal around the shank; metal caps are specified in the highest wind zones. One Florida product evaluation, for example, allows metal roofing nails with 3/8 in heads or 1 in plastic cap nails for a synthetic underlayment, specifies the 1 in plastic caps where wind or rain is expected before the roof covering goes on, and notes that the Florida code requires metal cap nails where the ultimate design wind speed is 150 mph (67 m/s) or more.3
Code requirements
High-wind attachment under the IRC and IBC
Under the 2021 International Residential Code and International Building Code, special underlayment rules apply where the design wind speed is 140 mph (63 m/s) or greater. Underlayment must then be two layers of ASTM D226 Type II or ASTM D4869 Type IV felt (or ASTM D6757 sheet), laid with a 19 in (483 mm) starter at the eaves and 19 in laps, and fastened with cap nails in a grid: 12 in (305 mm) between side laps, and 6 in (152 mm) on centre along the side and end laps. End laps must be at least 4 in (102 mm) and staggered at least 6 ft (1.8 m) apart.1 The IRC allows a self-adhered polymer-modified bitumen underlayment meeting ASTM D1970 as an alternative to the two-layer, cap-nailed system.1 Codes and manufacturers otherwise require underlayment to be fastened according to the manufacturer's installation instructions.2 See roof wind pressure zones and wind uplift.
Synthetic underlayments
The 2021 codes did not specifically address synthetic underlayments; NRCA-sponsored code changes approved for the 2024 IBC and IRC recognise underlayments meeting ASTM D8257, the standard for mechanically attached polymeric underlayments.1 In the meantime, acceptance has relied on product evaluations, whose fastening schedules are commonly stricter than for felt. One Florida-approved synthetic, for instance, calls for fasteners at 9 in (229 mm) centres along all laps and at 12 in (305 mm) centres in two staggered rows across the field of each sheet.3 The same evaluation limits how long the underlayment may stay exposed before roofing: 30 days for the lightest product and 180 days for heavier grades.3
For metal roofing, US metal-panel manufacturers point out that synthetic underlayments are acceptable under the IRC only when the panel manufacturer allows them, and that only D226 Type II or D4869 Type IV felts were listed for metal panels in high-wind areas.2
Installation practice
Typical practice with cap nails on a steep-slope roof is:13
- Roll out the underlayment with the printed lap lines aligned, starting at the eaves.
- Drive cap nails along the printed fastening marks or at the specified spacing — closer along laps and edges, wider in the field.
- Set the cap flat and snug against the sheet without crushing or cutting it; over-driven caps can tear synthetic sheets, and under-driven nails leave raised heads that telegraph through shingles or puncture metal panels.
- Keep fasteners out of valleys and other areas where they would sit under concentrated water flow unless the manufacturer allows it.
- Cover the underlayment with the roofing within the permitted exposure period.
Cap nails are also used to tack down ice barrier edges, insulation facers and slip sheets, and on walls to fasten house wrap and building paper.
Performance and problems
The cap's purpose is to resist pull-through: in wind tests, thin sheets fastened with plain nails tear around the shank, while the broader cap holds the sheet until much higher pressures. Problems seen in the field include:
- Too few fasteners or wrong spacing, leading to underlayment blow-off in storms before or after roofing — a frequent cause of water entry after hurricanes when the roof covering is also damaged (see hurricane roof damage and secondary water barrier).
- Staples or small-head nails used where cap fasteners are required, which tear out of synthetic sheets.
- Corrosion of uncoated metal caps or nails in coastal areas (see coastal corrosion).
- Leaks at fastener holes if the underlayment is left exposed and rain runs over it; caps reduce but do not eliminate this.
Where they are used
Cap nails are standard for synthetic and felt underlayments throughout North America, and are mandatory in the high-wind regions of the US Gulf and Atlantic coasts under the IRC, IBC and Florida Building Code.13
Sources
Reviewed 2 November 2026 · 3 sources · 3 cited inline · Editorial policy · Plain-text version · Suggest a correction
- Understanding underlaymentProfessional Roofing (NRCA) · professionalroofing.net
- Roofing Underlayment and Its Attachment RequirementsMBCI · mbci.com
- Evaluation Report FL16884-R4: TARCO synthetic underlaymentsFlorida Building Commission · floridabuilding.org